Please use this identifier to cite or link to this item: https://hdl.handle.net/10316/83197
Title: Estudo das condições higrotérmicas do Museu da Ciência da Universidade de Coimbra
Other Titles: Study of the hygrothermal conditions of the Museum of Science of the University of Coimbra
Authors: Costa, António Pedro Santos 
Orientador: Gaspar, Adélio Manuel Rodrigues
Pereira, Luisa Maria Dias
Keywords: Museu da Ciência da Universidade de Coimbra; Condições higrotérmicas; Conservação; Museum of Science of the University of Coimbra; Hygrothermal conditions; Conservation
Issue Date: 26-Sep-2017
Serial title, monograph or event: Estudo das condições higrotérmicas do Museu da Ciência da Universidade de Coimbra
Place of publication or event: Departamento Engenharia Mecânica
Abstract: O Museu da Ciência da Universidade de Coimbra (MCUC) está inserido num edifício construído em meados do século XVI. Sendo um edifício antigo, apresenta um microclima específico que nem sempre é benéfico para uma adequada preservação dos acervos presentes. Deste modo, um controlo efetivo das condições higrotérmicas (valores de humidade relativa e temperatura) no museu revela-se de extrema importância. É neste contexto que se enquadra a presente dissertação, tendo como principal objetivo a análise e avaliação das condições higrotérmicas em dez espaços do MCUC, desprovidos de sistemas de climatização, assim como o estudo relativo à concentração de dióxido de carbono presente apenas num espaço.De forma a avaliar o desempenho higrotérmico que o museu apresenta para a preservação do seu acervo, ao longo de um período de monitorização de aproximadamente seis meses, procedeu-se à recolha e subsequente tratamento de dados de humidade relativa, temperatura e dióxido de carbono, através, respetivamente, de sensores higrotérmicos e ferramentas informáticas. Esta avaliação foi feita com base em metodologias de três normas diferentes: EN 15757:2010, UNI 10829:1999 e ASHRAE:2015. Observou-se pelos resultados obtidos que o museu apresenta um clima muito instável, sendo influenciado pelas solicitações exteriores. Como consequência, os limites impostos pelas diferentes normas, de uma forma geral, não são cumpridos, sendo este, à partida, um fator prejudicial para a conservação do acervo museológico. Neste sentido, foram apresentadas algumas sugestões metodológicas que podem ser aplicadas com o objetivo de melhorar as atuais condições de preservação e conservação.
The Museum of Science of the University of Coimbra (MCUC) is housed in a building built in the mid-16th century. Being an old building, it presents a specific microclimate that is not always beneficial for an adequate preservation of the present collections. In this way, an effective control of the hygrothermal conditions (values of relative humidity and temperature) in the museum proves to be of extreme importance. It’s in this context that the present dissertation is framed, having as main objective the analysis and evaluation of the hygrothermal conditions in ten rooms of the MCUC, devoid of air conditioning systems, as well as the study concerning the concentration of carbon dioxide present in only one room.In order to evaluate the hygrothermal performance of the museum for the preservation of its collection, during a monitoring period of approximately six months, data were collected and subsequently processed for relative humidity, temperature and carbon dioxide, through respectively, hygrothermal sensors and computer tools. This evaluation was based on methodologies of three different standards: EN 15757:2010, UNI 10829:1999 and ASHRAE:2015.It was observed from the results obtained that the museum presents a very unstable climate, being influenced by external requests. As a consequence, the limits imposed by the different standards, in a general way, are not fulfilled, being this, a negative factor for the conservation of the museum collection. In this sense, some methodological suggestions have been presented that can be applied in order to improve the current conditions of preservation and conservation.
Description: Dissertação de Mestrado Integrado em Engenharia do Ambiente apresentada à Faculdade de Ciências e Tecnologia
URI: https://hdl.handle.net/10316/83197
Rights: embargoedAccess
Appears in Collections:UC - Dissertações de Mestrado

Files in This Item:
File Description SizeFormat
Dissertação final - António Costa.pdf2.69 MBAdobe PDFView/Open
Show full item record

Page view(s) 50

483
checked on Apr 16, 2024

Download(s) 50

372
checked on Apr 16, 2024

Google ScholarTM

Check


This item is licensed under a Creative Commons License Creative Commons