dc.identifier.citationPARREIRAL, Ana Rita Vaz - Caracterização da qualidade do ambiente interior num edifício escolar recentemente requalificado [em linha]. Disponível em URL: http://hdl.handle.net/10316/19972. Coimbra : [s.n.], 2011. Dissertação de mestrado-
dc.identifier.urihttps://hdl.handle.net/10316/19972-
dc.description.abstractEsta dissertação tem como objectivo a caracterização da qualidade do ambiente interior do Bloco C, da Escola Básica 2,3 Dr. José Lopes de Oliveira, que recentemente foi alvo de uma intervenção de reabilitação. Para a concretização deste objectivo foram efectuadas medições das concentrações de CO2 e PM10, da temperatura e da humidade relativa do ar interior, níveis de iluminação e de ruído no interior de algumas salas do Bloco C. Posteriormente foi efectuado o tratamento dos dados registados e verificadas as suas conformidades com a legislação actual. Os caudais de ar novo efectivos em cada uma das salas foram obtidos através das taxas de renovação de ar, determinadas pela aplicação da técnica dos gases traçadores em período de decaimento da concentração. Neste caso, usou-se como gás traçador o CO2 emitido pelos ocupantes (CO2 metabólico). Conhecidos os valores dos caudais de ar novo efectivos, foram comparados com os caudais de ar novo adequados às diferentes salas monitorizadas, de modo a que a média da concentração de CO2 no período considerado apresentasse conformidade com a legislação (< 1500 ppm). Foi, assim, possível determinar quais as salas que apresentavam um défice de ar novo. No que diz respeito à iluminação, foram comparados os valores dos níveis de iluminação natural e artificial, em cada sala analisada. Para a caracterização do conforto acústico procedeu-se à verificação da conformidade do nível de ruído resultante do sistema de ventilação. Da observação de todos os resultados obtidos concluiu-se que a qualidade do ambiente interior não é uniforme em todas as salas e que se verificam poucas conformidades com a legislação.-
dc.description.abstractThis thesis intends to characterise the air indoor environmental quality in Building C of Escola Básica 2,3 Dr. José Lopes de Oliveira, which was recently renovated. For that purpose, CO2 and PM10 concentration, temperature and relative humidity of indoor air, lighting and noise levels were measured inside some of the rooms in Building C. Then, logged data was processed and its conformity to current legislation verified. Actual fresh air flow in each of the rooms was obtained through air renewal rates calculated by applying the tracer gas method in the concentration decay period. In this case, the tracer gas used was CO2 released by building occupants (metabolic CO2). Once actual fresh air flow values were ascertained, they were compared with fresh air flows suitable for the various monitored rooms, so the average CO2 concentration during the analysed period would conform to legislation (< 1500 ppm). This meant it was possible to establish which rooms presented a fresh air shortage. As far as lighting is concerned, values of natural and artificial light levels were compared in each of the analysed rooms. In order to characterise acoustic comfort, conformity of the noise level resulting from ventilation system operation was assessed. Analysis of all data obtained led to the conclusion that the indoor environmental quality inside all rooms is not uniform and that conformity to legislation only occurs in few cases.-
dc.language.isoporpor
dc.rightsopenAccesspor
dc.subjectQualidade do ambiente interiorpor
dc.subjectCaudal de ar novo-
dc.subjectTaxa de renovação de ar-
dc.subjectNível de iluminação-
dc.subjectNível de ruído-
dc.titleCaracterização da Qualidade do Ambiente Interior num Edifício Escolar Recentemente Requalificadopor
dc.typemasterThesispor
dc.peerreviewedNopor
item.openairecristypehttp://purl.org/coar/resource_type/c_18cf-
item.openairetypemasterThesis-
item.cerifentitytypePublications-
item.grantfulltextopen-
item.fulltextCom Texto completo-
item.languageiso639-1pt-
crisitem.advisor.researchunitLAETA - Associated Laboratory for Energy, Transports and Aeronautics-
crisitem.advisor.researchunitADAI - Association for the Development of Industrial Aerodynamics-
crisitem.advisor.orcid0000-0002-7015-6989-
Appears in Collections:UC - Dissertações de Mestrado
FCTUC Eng.Mecânica - Teses de Mestrado
Show simple item record

Google ScholarTM

Check


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.