dc.description.abstractFault-tolerance is critical in power electronics, especially in Uninterruptible Power Supplies, given their role in protecting critical loads. Hence, it is crucial to develop fault-tolerant techniques to improve the resilience of these systems. This paper proposes a non-redundant fault-tolerant double conversion uninterruptible power supply based on 3-level converters. The proposed solution can correct open-circuit faults in all semiconductors (IGBTs and diodes) of all converters of the system (including the DC-DC converter), ensuring full-rated post-fault operation. This technique leverages the versatility of Finite-Control-Set Model Predictive Control to implement highly specific fault correction. This type of control enables a conditional exclusion of the switching states affected by each fault, allowing the converter to avoid these states when the fault compromises their output but still use them in all other conditions. Three main types of corrective actions are used: predictive controller adaptations, hardware reconfiguration, and DC bus voltage adjustment. However, highly differentiated corrective actions are taken depending on the fault type and location, maximizing post-fault performance in each case. Faults can be corrected simultaneously in all converters, as well as some combinations of multiple faults in the same converter. Experimental results are presented demonstrating the performance of the proposed solution.pt
dc.language.isoengpt
dc.publisherMDPI AGpt
dc.relationProject SAICT-45-2017-POCI-01-0145-FEDER- 029112—PTDC/ EEI-EEE/29112/2017pt
dc.relationUIDB/EEA/50008/2020pt
dc.rightsopenAccesspt
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/pt
dc.subjectpower electronicspt
dc.subjectmultilevel converterspt
dc.subjectfault tolerancept
dc.subjectmodel predictive controlpt
dc.titleFault Analysis and Non-Redundant Fault Tolerance in 3-Level Double Conversion UPS Systems Using Finite-Control-Set Model Predictive Controlpt
dc.typearticlept
degois.publication.firstPage2210pt
degois.publication.issue8pt
degois.publication.titleEnergiespt
dc.peerreviewedyespt
dc.identifier.doi10.3390/en14082210-
degois.publication.volume14pt
dc.date.embargo2021-01-01*
uc.date.periodoEmbargo0pt
item.cerifentitytypePublications-
item.languageiso639-1en-
item.fulltextCom Texto completo-
item.grantfulltextopen-
item.openairecristypehttp://purl.org/coar/resource_type/c_18cf-
item.openairetypearticle-
crisitem.author.orcid0000-0002-7529-5670-
Appears in Collections:I&D IT - Artigos em Revistas Internacionais
FCTUC Eng.Electrotécnica - Artigos em Revistas Internacionais
Show simple item record

WEB OF SCIENCETM
Citations

1
checked on May 2, 2023

Page view(s)

70
checked on May 22, 2024

Download(s)

45
checked on May 22, 2024

Google ScholarTM

Check

Altmetric

Altmetric


This item is licensed under a Creative Commons License Creative Commons