Title: | Simulation-based analysis of the use of PCM-wallboards to reduce cooling energy demand and peak-loads in low-rise residential heavyweight buildings in Kuwait | Authors: | Soares, N. Reinhart, C.F. Hajiah, A. |
Keywords: | PCM-wallboards; residential buildings; hot arid climate; cooling energy demand; dynamic simulation | Issue Date: | Aug-2017 | Publisher: | Springer | Project: | PCMs4Buildings POCI-01-0145-FEDER-016750 PTDC/EMS-ENE/6079/2014 SFRH/BD/51640/2011 |
metadata.degois.publication.title: | Building Simulation | metadata.degois.publication.volume: | 10 | metadata.degois.publication.issue: | 4 | Abstract: | Between 2000 and 2015, annual electric peak demand in Kuwait has doubled to 15000 MW and the Ministry of Energy and Water expects this number to double once more by 2030 attributing 70% of this growth to new housing projects. Within this context, this manuscript evaluates the effect of incorporating PCM-wallboards in low-rise air-conditioned residential heavyweight buildings in Kuwait. Using an EnergyPlus single-zone model, a parametric study is performed considering several window-to-wall ratios (WWRs), different solar orientations and some PCM-wallboards configurations. The main study goals are to: (i) explore the validity of a single PCM-wallboard solution that can be universally applied throughout residential buildings in Kuwait; (ii) evaluate the impact of PCMwallboard on the reduction of both cooling demand and peak-loads; (iii) provide some guidelines for incorporating PCM-wallboards in Kuwait. Following an extensive parametric study, a 4 cm thick PCM-wallboard with a melting-peak temperature of 24 °C yielded the lowest annual cooling demand across a variety of room orientations and WWRs assuming cooling setpoint of 24 °C. Its implementation led to annual cooling energy savings of 4%–5% across all the case-studies. Regarding the impact throughout the year, cooling demand and peak-loads can be reduced by 5%–7% during summer months. The average daily cooling loads can be reduced by 5%–8%. | URI: | https://hdl.handle.net/10316/42004 | ISSN: | 1996-3599 (Print) 1996-8744 (Online) |
DOI: | 10.1007/s12273-017-0347-2 | Rights: | openAccess |
Appears in Collections: | FCTUC Eng.Mecânica - Artigos em Revistas Internacionais |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
Simulation-based analysis of the use of PCM-wallboards to reduce cooling energy demand and peak-loads in low-rise residential heavyweight buildings in Kuwait.pdf | 1.31 MB | Adobe PDF | View/Open |
SCOPUSTM
Citations
45
checked on Oct 28, 2024
WEB OF SCIENCETM
Citations
5
42
checked on Nov 2, 2024
Page view(s) 50
628
checked on Nov 6, 2024
Download(s) 50
753
checked on Nov 6, 2024
Google ScholarTM
Check
Altmetric
Altmetric
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.